126 kV 2500 A 40 kA GIS

126 kV 2500 A 40 kA GIS

1
Rated voltage
kVrms 126
2
Rated current
Arms 2500/3150
3
Rated frequency
Hz 50/60
4
Rated frequency
kArms 40
5
Rated peak withstand current
kApeak 100
6
Rated short-time withstand current (3 sec)
kArms 40
7
Rated power frequency withstand voltage (1 min)
kVrms 230/265
8
Rated lightning impulse withstand voltage
kVpeak 550/630
9
Opening time
ms < 30
10
Closing time
ms < 100
11
Breaking time
ms < 50
12
CB rated operating sequence
- O-0.3 s-CO-180 s-CO
13
Rated short-line fault current (L75/L90)
kArms 30/36
14
Rated out-of-phase current
kArms 10
15
Rated line-charging breaking current
Arms 31.5
16
Rated line-charging breaking current
Arms 140
17
Rated SF6 gas pressure (20℃)
MPa 0.6
18
SF6 gas leakage
%/year 0.5
19
Type of operating mechanism (CB)
- Spring type