72.5 kV 2000 A 40 kA G.I.S

72.5 kV 2000 A 40 kA G.I.S

1
Rated Voltage
kVrms
72.5
2
Rated Current
Arms
2000
3
Rated frequency
Hz
50/60
4
Rated short-circuit breaking current
kArms
40
5
Rated short time making current
kApeak
104
6
Rated short time withstand current(3 s)
kArms
40
7
Rated power-frequency withstand Voltage
kVrms
160
8
Rated Lightning impulse withstand Voltage
kVpeak
350
9
Opening time
ms
< 35
10
Closing time
ms
< 100
11
Breaker time
ms
< 50
12
Rated operating sequence
-
O-0.3 s-CO-180 s-CO
13
Short-line fault breaking current(L75/L90)
kArms
30/36
14
Rated out-of-phase breaking current
kArms
10
15
Rated line-charging breaking current
Arms
10
16
Rated cable-charging breaking current
Arms
125
17
Rated gas pressure
MPa
0.6

18

SF6 leakage rate

%year

< 0.5

19

Method operation

-

spring

72.5 kV GIS設備配置圖

72.5 kV GIS設備構造圖