161 kV 2000 A 50k A GIS (Hyd-1.8m)

161 kV 2000 A 50k A GIS (Hyd-1.8m)

1
Rated voltage
kVrms
161
2
Rated maximum voltage
kVrms
169
3
Rated frequency
Hz
60
4
Rated current
Arms
2000/4000
5
Rated short-circuit breaking current
kArms
50
6
Rated short time withstand current (3s)
kArms
50
7
Rated short time withstand current (3s)
kVrms
365
8
Rated lightning impulse withstand voltage
kVpeak
750
9
Rated breaking time
cycle
3
10
Rated delay trip time
second
1
11
Standard duty cycle for breaker
-
CO-15sec-CO
12
Operation duty cycle for breaker
-
O-20cycle-CO
13
Rated pressure (20℃)
kgf/cm.G
6
14
SFleakage rate
% / year
0.5
15
Control voltage
DC(V)
125
16
Control voltage
-
Hydraulic

161 kV GIS(液壓操作型1.8 m)單線圖

161 kV GIS(液壓操作型1.8 m)設備構造圖LINE BAY

161 kV GIS(液壓操作型1.8 m)設備構造圖TIE BAY

161 kV GIS(液壓操作型1.8 m)設備構造圖TR BAY

161 kV GIS(液壓操作型1.8 m)設備構造圖BUSPT