69 kV 2000 A 25/40 kA G.I.S

69 kV 2000 A 25/40 kA G.I.S

Main technical data

1

Rated Voltage

kVrms 69
2

Rated maximum Vottage

kVrms 72.5
3

Rated frequency

Hz 60
4

Rated Current

Arms 2000
5

Rated short-circuit breaking current

kArms 40
6

Rated short time withstand current(3s)

kArms 40
7

Rated power-frequency withstand Voltage

kVrms 160
8

Rated Lightning impulse withstand Voltage

kVpeak 350
9

Rated breaking time

cycle 5
10

Rated delay trip time

second 2
11

Standard duty cycle for breaker

- CO-15sec-CO
12

Standard duty cycle for breaker

- O-0.3sec-CO
13

Rated pressure(20℃)

kgf/cm2.G 6
14

SF6 leakage rate

% / year 0.5
15

Control Vottage

DC(V) 125 / 24
16

Operation mechanism for breaker

- spring

69 kV GIS single line diagram

69 kV GIS layout

69 kV GIS structure diagram LINE BAY

69 kV GIS structure diagram TIE BAY

69 kV GIS structure diagram TR BAY

69 kV GIS structure diagram BPT BAY