161 kV 2000 A 50 kA G.C.S

161 kV 2000 A 50 kA G.C.S

Type: FLLE-140-50

 

Main technical data:

 
1
Rated Voltage
kVrms
161
2
Rated Voltage
kVrms
169
3
Rated frequency
Hz
60
4
Rated Current
Arms
2000
5
Rated short-circuit breaking current
kArms
50
6
Rated short time withstand current(3 s)
kArms
50
7
Rated power-frequency withstand Voltage
kVrms
365
8
Rated Lightning impulse withstand Voltage
kVpeak
750
9
Rated Lightning impulse withstand Voltage
kVpeak
NOTE
10
Rated breaking time
cycle
3
11
Rated delay trip time
second
1
12
Standard duty cycle for breaker
-
CO+15sec+CO
13
Operation duty cycle for breaker
-
O+20cycle+CO
14
Rated pressure(20 ℃)
kgf/cm2.G
6
15
SF6 leakage rate
%/year
0.5
16
Control Vottage
DC(V)
125
17
Operation mechanism for breaker
-
Operation mechanism for breaker

Layout

Structure diagram