161 kV 2000 A 50 kA G.C.S
Type: FLLE-140-50
Main technical data:
1
|
Rated Voltage
|
kVrms
|
161
|
2
|
Rated Voltage
|
kVrms
|
169
|
3
|
Rated frequency
|
Hz
|
60
|
4
|
Rated Current
|
Arms
|
2000
|
5
|
Rated short-circuit breaking current
|
kArms
|
50
|
6
|
Rated short time withstand current(3 s)
|
kArms
|
50
|
7
|
Rated power-frequency withstand Voltage
|
kVrms
|
365
|
8
|
Rated Lightning impulse withstand Voltage
|
kVpeak
|
750
|
9
|
Rated Lightning impulse withstand Voltage
|
kVpeak
|
NOTE
|
10
|
Rated breaking time
|
cycle
|
3
|
11
|
Rated delay trip time
|
second
|
1
|
12
|
Standard duty cycle for breaker
|
-
|
CO+15sec+CO
|
13
|
Operation duty cycle for breaker
|
-
|
O+20cycle+CO
|
14
|
Rated pressure(20 ℃)
|
kgf/cm2.G
|
6
|
15
|
SF6 leakage rate
|
%/year
|
0.5
|
16
|
Control Vottage
|
DC(V)
|
125
|
17
|
Operation mechanism for breaker
|
-
|
Operation mechanism for breaker
|