550 kV LT G.C.B

550 kV LT G.C.B

Main technical data:

 
1
Rated Voltage
kVrms
550
2
Rated Current
Arms
6000
3
Rated frequency
Hz
50
4
Rated frequency
kArms
40
5
Rated withstand current
kApeak
170
6
Rated short time making current
kArms
170
7
Rated short time withstand current(3 s)
kArms
63
8
Rated power-frequency withstand Voltage
kVrms
740/1055
9
Rated Lightning impulse withstand Voltage
kVpeak
1675/1675+450
10
Opening time
ms
< 20
11
Closing time
ms
< 100
12
Breaker time
ms
< 40
13
Rated operating sequence
-
O-0.3 s-CO-180 s-CO
14
Short-line fault breaking current(L75/L90)
kArms
47.25/56.7
15
Rated out-of-phase breaking current
kArms
15.75
16
Rated line-charging breaking current
Arms
500
17
Rated cable-charging breaking current
Arms
500
18
Rated gas pressure
MPa
0.6/0.5
19
First-pole-to-clear-factor
pu
1.3
20
Method operation
-
Hydraulic
21
Type operation
-
Single pole

550 kV structure diagram of high voltage cylinder-type