252 kV LT G.C.B

252 kV LT G.C.B

Main technical data:

 
1
Rated Voltage
kVrms
252
2
Rated Voltage
Arms
4000/4800
3
Rated frequency
Hz
50
4
Rated frequency
kArms
50
5
Rated withstand current
kApeak
135
6
Rated short time making current
kArms
135
7
Rated short time withstand current(3 s)
kArms
50
8
Rated power-frequency withstand Voltage
kVrms
460/605
9
Rated Lightning impulse withstand Voltage
kVpeak
1050/1050+150
10
Opening time
ms
< 21
11
Closing time
ms
< 100
12
Breaker time
ms
< 40
13
Rated operating sequence
-
O-0.3 s-CO-180 s-CO
14
Short-line fault breaking current(L75/L90)
kArms
37.5/45
15
Rated out-of-phase breaking current
kArms
12.5
16
Rated line-charging breaking current
Arms
160
17
Rated cable-charging breaking current
Arms
250
18
Rated gas pressure
Mpa
0.6/0.5
19
Frist-pole-to-clear-factor
pu
1.5
20
Frist-pole-to-clear-factor
-
Spring
21
Type operation
-
Single/Triple pole

252 kV structure diagram of high voltage cylinder-type