145kV 3150A 40kA L-T GCB

145kV 3150A 40kA L-T GCB

Main parameters:

 
Circuit Breaker (CB) Type form OFPI-145-40L-FAR3
Rated voltage 145 kV
Rated frequency 50 Hz
Rated current 3150 A
First-pole-to-clear factor 1.5
Rated short-circuit breaking current(4s) 40 kA
Breaking time < 60ms
Rated short-circuit making current 108 kA
Rated short-time withstand current 40 kA
Rated peak withstand current 108 kA
Making capacity in short-line fault conditions (L75/L90) 30 / 36 kA
Rated out-of-phase breaking current 10 kA
Line charging breaking current 31.5 A
Cable charging breaking current 140 A
Power frequency withstand voltage 275 / 315 kV
Lightning impulse withstand voltage 650 / 650+100 kV
Rated SF6 gas pressure 0.6 Mpa.G
Operating type Spring

145kV GCB structure diagram