Taipei Veterans General Hospital - 2000kW Generator Set

Taipei Veterans General Hospital - 2000kW Generator Set

Work Scope:

Design, manufacturing, assembly, inspection, testing, and trial operation of generator, arrangement and construction for emergency power supply.

Specifications:

1. 2,000kW 380/220V 0.8pf 60Hz 1,800rpm.

2. Manufacturing standards: NEMA, CNS and ISO standards.

3. Water-cooled, 4-stroke, 16-cylinder diesel engine specially designed for generator, along with its accessories.

4. Generator with a two-bearing design, an IP21 enclosure, self-ventilated cooling, Class H insulation, Class B temperature rise, insulation and dielectric strength meeting NEMA MG1-22 standards.

Ambient:

1. Location: at an altitude below 1,000m.

2. Temperature: 5-40.

3. Humidity: 90% RH max.